High purity electrolytic grade bright annealed flexible bunched bare copper conductor confirming to International Standards such as IS-8130, BS-6360, IEC 228 & VDE-0295.
» Insulation
Oil & Water Resistant Heavy Duty Tough & Flexible Thermoplastic Elastomer Compound (TPE/TPR)
Cross
section
area
(nom.)
sq.mm
Insulation thickness (nom.)
mm
Overall diameter (approx.)
mm
Conductor
resistance at 20° C (max.)
ohm/Km
Current
carrying
capacity
amps.
16
2
9.7
1.21
81
25
2
11.1
0.78
105
35
2
12.4
0.554
125
50
2.2
14.4
0.386
160
70
2.4
17.1
0.272
195
95
2.6
19.5
0.206
235
120
2.8
21.5
0.161
270
150
3
23.9
0.129
305
185
3.2
26.3
0.106
350
240
3.4
29.7
0.0801
405
Note :